Parameter Selection Guidelines for Direct-on-Line Permanent Magnet Generators Contemplating Fault-Ride-Through Capability

Kinnunen, Pietu; Lindh, Pia; Zadorozhniuk, Daniil; Pyrhönen, Juha; Parviainen, Asko (2022-12-01)

Katso/Avaa
kinnunen_et_al_parameter_selection_final_draft.pdf (2.259Mb)
Lataukset: 


Post-print / Final draft

Kinnunen, Pietu
Lindh, Pia
Zadorozhniuk, Daniil
Pyrhönen, Juha
Parviainen, Asko
01.12.2022

IEEE Access

10

128166-128176

IEEE

School of Energy Systems

https://doi.org/10.1109/ACCESS.2022.3225917
Näytä kaikki kuvailutiedot
Julkaisun pysyvä osoite on
https://urn.fi/URN:NBN:fi-fe2022121972589

Tiivistelmä

Direct-on-line (DOL) driven permanent-magnet generators (PMSGs) are often applied in small-scale hydropower plants (< 10 MW). The Commission Regulation (EU) 2016/631 defines the boundary conditions to operate these generators in parallel with the grid. According to the regulation, fault-ride-through (FRT) capability is required in some cases. FRT scenario of PMSGs was studied by simulations and the importance of machine parameters was analyzed. Machine parameters under interest are damper winding resistance and leakage inductance, stator resistance and leakage inductance, saliency, source voltage, total inductance and system inertia. Authors proved that fault-ride-through can be achieved by utilizing smart machine parameters selection without using complicated control systems and auxiliary equipment. FRT simulations are performed for three PMSGs and their capabilities are explored. Results can be used as a guideline in DOL PMSG design for satisfying FRT requirements. The simulation system was also verified with measurements of a 600 kW PMSG data during a fault situation: an incident where the generator was connected to the grid in phase opposition.

Lähdeviite

Kinnunen, P., Lindh, P., Zadorozhniuk, D., Pyrhönen, J., Parviainen, A. (2022). Parameter Selection Guidelines for Direct-on-Line Permanent Magnet Generators Contemplating Fault-Ride-Through Capability. IEEE Access, vol. 10. pp. 128166-128176. DOI: 10.1109/ACCESS.2022.3225917

Kokoelmat
  • Tieteelliset julkaisut [1139]
LUT-yliopisto
PL 20
53851 Lappeenranta
Ota yhteyttä | Tietosuoja | Saavutettavuusseloste
 

 

Tämä kokoelma

JulkaisuajatTekijätNimekkeetKoulutusohjelmaAvainsanatSyöttöajatYhteisöt ja kokoelmat

Omat tiedot

Kirjaudu sisäänRekisteröidy
LUT-yliopisto
PL 20
53851 Lappeenranta
Ota yhteyttä | Tietosuoja | Saavutettavuusseloste